Model PD750 Universal/Temperature Meter
The PD750 temperature meter handles temperature displaying, alarming and
re-transmitting applications with simplicity, accuracy and reliability. The
PD750 is available with up to 4 relays, isolated 4-20 mA output, and is factory
programmed for easy field selection of the thermocouple or RTD type. Just select
your input type (J,K,T,E,R,S thermocouple or 100 ohm RTD), and either Fahrenheit
or Celsius and connect the sensor.
- One Model Handles Thermocouples and RTD Inputs
- J,K,T,E,R, & S Thermocouples*
- Platinum RTD (0.00385 or 0.00392 curve)*
- Type T T/C and RTD's displayed to 0.1 deg *
- Displays F or C* - No Calibration Necessary
- NEMA 4X Front Panel
- 2 or 4 Relays + 4-20 mA Output Option
*field selectable
4 Visual Alarms standard
- Front panel Alarm Status Indication
- Perfect for Visual-indication-only Applications
- Any combination of high or low set points
- 0-100% dead-band adjustments
Options
2 or 4 relays
- two or four SPDT, 2 amps @ 240Vac resistive
- Automatic or automatic + manual reset
- Fail-safe action and auto initialization
- 0-100% dead-band adjustment
Isolated 4-20mA transmitter output
- 4-20 mA or 20-4 mA output
- 500 Vdc isolation
- Can be scaled over narrow range
- With or without relay contacts
| Pre-calibrated Ranges |
| Input |
Range |
Accuracy |
| Type J |
-328 to 1382 deg F |
+/-1.4 deg F |
| |
-200 to 750 deg C |
+/- 0.8 deg C |
| Type K |
-328 to 2498 deg F |
+/- 1.7 deg F |
| |
-200 to 1330 deg C |
+/-0.9 deg C |
| Type T |
-330.0 to 760.0 deg F |
+/-1.5 deg F* |
| |
-200. To 404.0 deg C |
+/-0.8 deg C** |
| Type E |
-328 to 1832 deg F |
+/- 1.4 deg F |
| |
-200 to 1000 deg C |
+/-0.8 deg C |
| Type R |
32 to 3212 deg F |
+/-4.8 deg F |
| |
0 to 1767 deg C |
+/- 2.7 deg C |
| Type S |
40 to 3214 deg F |
+/-5.7 deg F |
| |
4 to 1768 deg C |
+/-2.9 deg C |
| 100 ohm RTD |
-328 to 1382 deg F |
+/-0.6 deg F |
| |
-200 to 750 deg C |
+/-0.3 deg C |
| *The accuracy from -450 to -331 deg F is +/-4.6 deg F |
| **The accuracy from -263 to -201 deg C is +/-2.6 deg C |
Specifications
Basic Meter
- Display
: Bright, large, 0.56" (14.2 mm) high efficiency red LED,
4 ˝ digits. F or C may be switched on to indicate Fahrenheit or Celsius.
- Cold Junction Reference
: Automatic, fixed , no user calibration
needed.
- TC Open Indication
: Open thermocouple circuit indicated by flashing
display. Status of relays determined by setting.
- Hold Reading
: Connect switch to ACK/HLD and COM terminals, also
connect jumper pins at rear.
- Input Impedance
: Greater than 100 Kohms.
- Power
: 115 VAC or 230 VAC +/- 10%, 50/60 Hz, 10 VA.
- Enclosure
: 1/8 DIN, high impact plastic, UL 94V-0.
- Front Panel
: NEMA 4X, panel gasket provided.
- Connections
: Removable screw terminal block (provided), accepts 24 to
12 AWG
- Alarm Points
: 4,any combination of high or low alarms,
- Alarm Status
Indication: Front panel LED
- Alarm Dead-band
: 0-100 % of full scale, field selectable.
Relays
- Ratings
: Two or four relays, 2 Amp SPDT (form C).
- Contacts:
2 A @ 30 Vdc or 2 A @ 250 Vac resistive; 1/14 HP @ 125/250
Vac for NC contacts and 1/10 HP @ 120/250 Vac fo NO contacts, inductive load
- Reset
: User select
- automaticly when the input passes the reset point
- aoutomaticly +manually (via user supplied switch of front panel ACK
button)
- Fail-safe operation
: the relays are energized in the non-alarmed
condition. In the case of a power failure, the relays will go to the alarm
state. May be disable with internal jumper.
- Auto initialization
: When power is appled to the meter the relays will
always reflect the state of the input to the meter.
- Dead-band
: 0-100%, User selectable
Isolated 4-20 mA Transmitter output
- Calibrated Range
: Anywhere in range of meter, 501 count minimum range
- Output Loop Resistance
: 1500 ohms max. using a 35V external power
supply, 500 ohms max. using the built-in loop power supply.
- Loop Power
: Isolated, up to 20 mA at 24 Vdc regulated, noise less than
10 mV p-p.
- External loop power Supply
: 35V max.
- Accuracy
: +/- 0.1% FS, +/- .004 mA
- Isolation
: 500 Vdc or peak AC, input-to-input or input/output-to-power
line.

| model |
description |
| PD750-3-N |
No options |
| PD750-3-14 |
2 relays |
| PD750-3-15 |
4-20 mA output |
| PD750-3-16 |
2 Relays + 4-20 mA output |
| PD750-3-17 |
4 relays |
| PD750-3-18 |
4 relays + 4-20 mA output |
| PDX-6901 |
Snubber for inductive loads |
| Use a -4 instead of a -3 to specify 230 Vac powered meters at no
extra cost. |
Prices subject to change.
bookmark this page
 |
3209 W.9th street
Lawrence, KS 66049
USA
|
phone (785) 841 3089
FAX (785) 841 0434
E-mail inform@xtronics.com
WEB http://www.xtronics.com |
 |
Corporate information and privacy
statement
(C) Copyright 1994-2006, Transtronics, Inc. All rights reserved
Transtronics® is a registered trademark of Transtronics, Inc.