Model PD695 4 ½ Digit RMS AC VoltmeterPicture of a PD690

***Just One Button To Program And Calibrate****

Applications:

·       Power-line monitor- Shut down operations before your power is completely down.

·       Set-point controller - Start or stop any operation on your programmed set point

Model PD695 is a high performance, digital process meter.

·       Easy Single Button Scaling

·       50 mVac 200mVac 2 Vac 20Vac and 250 Vac Field Selectable Inputs

·       24 V Transmitter Power Supply Standard

·       Stand Alone Scaling

·       Steady, Accurate Display to +/- 199,990

·       Field programmable noise filter

·       Peak display

·       4 ½ Digit + Extra Zero

·       NEMA 4X Front Panel

·       2 or 4 Relay = 4-20 mA Output Options

calibrate picture

Stand alone scaling allows the PD695 to be scaled without applying an input. Simply select internal calibration (I-CAL) mode and set desired display for the 4mA and 20 mA value. To scale first complete an initial calibration.

4 Visual Alarms Standard

·       Front panel alarm status indication

·       Perfect for 'Visual indication only' applications

·       any combination of high or low set points

·       0-100% dead-band adjustment

Big bright steady display for big numbers

·       4 ½ digit + extra zero display

·       Displays up to +/- 199,990

·       0.56" high efficiency red LED's

·       Steady and quick responding display

Powers the loop

·       The 24 Volt transmitter power supply is standard on the PD695. This feature saves time and money by simplifying wiring and eliminating the cost of an external transmitter power supply.

NEMA 4X Front Panel

·       Wet, dirty and dusty environments don't bother the PD695's NEMA 4X front panel so it can be installed in almost any panel in the plant

Linearization

·       The linearization feature has two modes of operation:

·       The 11 point user calibration displays non-linear signals

·       The square root extraction displays the flow rate from a differential transmitter.

Programmable Noise Filter

·      Programmable update rate for steady display

·      Adjustable noise window

Remember every PD695 comes with 4 visual alarms standard!

The PD695 RMS AS voltmeter can be equipped with 2 or 4 relay contacts and a isolated 4-20 mA transmitter output. These options may be combined in any configuration to satisfy a wide variety of applications. A fully loaded model PD695-3 includes 4 relays and a isolated 4-20 mA transmitter output.

Two or four Relays

·       2 or 4 SPDT, 2A @240Vac resistive

·       Automatic or automatic + manual reset

·       Fail-safe action and auto initialization

·       0-100% dead-band adjustment

Isolated 4-20 mA output

·       4-20mA or 20-4 mA output

·       500 Vdc isolation

·       With or without relay contacts

Specifications-Basic Meter

·       Inputs: Field Selectable: 50 mV, 200 mV, 2V 20V 250V RMS and RMS peak

·       Display: Bright, Large, 0.56" (14.2mm) high efficiency red LED. 4 ½ digits + extra zero; +/- 1999(0), (0) may be switched on to display 199,990. Leading zeros can be blanked

·       Display Rate : up to 2/second

·       Crest factor : 5:1

·       Loop Power : Isolated 24 VDC at 20mA regulated. Noise less than 10 mV p-p. Max loop resistance of 1200 ohms. Available for either signal input or 4-20 mA output option, but not both.

·       Accuracy : 0.1% of full scale at 60 Hz.

·       Resolution : 0.025 of full scale

·       Hold reading or External Acknowledge : Connect ACK/HLD and COM and select JP5 on rear to change from ACK to hold

·       Lockout: JP6 at rear of instrument restricts modification of calibration values.

·       Input Impedance : Greater than 1 Mohms: Current range,100 ohms.

·       Power : 115 VAC +/- 10%, 50/60 Hz, 10 VA.

·       Isolation : 1500Vac

·       Environmental : Operating temperature range: 0 to 65 deg C. Storage Temperature range : -40 to 85 deg C. Relative Humidity : 0 to 90% non-condensing.

·       Enclosure : 1/8 DIN, high impact plastic, UL 94V-0.

·       Front Panel: NEMA 4X, panel gasket provided.

·       Connections : Removable screw material block (provided). Accepts #22 to #12 AWG.

·       Alarm Points : 4,any combination of high or low alarms.

·       Alarm Status Indication; Front Panel LED

·       Alarm Dead-band : 0-100%, User Selectable.

·       Warranty : 1 year parts and labor.

·       Calibration : Maybe calibrated using internal calibration (I-CAL) or by applying an external calibration signal (E-CAL).

Relays

·       Rating : 2 or 4 relays; 2 Amp SPDT (form C). The contacts are rated 2 Amp @ 30 VDC or 2 Amp @ 250 VAC resistive load; 1/14 HP @ 125/250 VAC for NC contacts and 1/10 HP @ 125/250 VAC for NO contacts, inductive load.

·       Reset : User Select.

1.     1. Automatically when the input passes the reset point.

2.     2. Automatically + manually (via user supplied switch or front panel ACK button).

·       Fail-safe Operation : The relay coils are energized in the non-alarm condition. In the case of a power failure , the relays will go to the alarm state. May be disabled with internal jumper.

·       Auto Initialization : When power is applied to the meter, the relays will always reflect the state of the input to the meter.

·       Dead band : 0-100 %, User Selectable.

Isolated 4-20 mA Transmitter Output:

·       Calibration Range: Anywhere in range of meter, 501 count minimum span.

·       Output Loop Resistance : 1500 ohms max. using a 35V external power supply. 500 ohms max. using the built-in loop power supply. Built-in loop power supply available for either 4-20 mA output or signal input, but not both.

·       Accuracy : +/- 0.1% FS, +/- .004 mA

·       Isolation: 500 VDC or peak AC, input-to-output or input/output-to-power line.

· External Loop Power Supply : 35 V max.

·      

PD695-3-N No options   298  Check stock on PD695 seriies
PD695-3-14 2 Relays  258
PD695-3-15 4-20mA Output  397
PD695-3-16 2 Relays + 4-20 mA output  457
PD695-3-17 4 Relays 473
PD695-3-18 4 Relays + 4-20 mA output 528
A -4 may be substituted for the -3 to call out meters powered from 230Vac at no extra charge.
Options
Option number Description
PDX-6901 Snubber (for relays powering inductive loads)

Hot tip - Green Lee (800 435 0786) has a 1/8th DIN panel punch part # 60068 for the NEMA 4X bezels.


prices subject to change

Transtronics Home Page
See our line of industrial control electronics
Back to PLC'sIndex Resource library handbooks, primers and spec sheets. Process Control
Panel Meters
4sale4sale E-mail pd@xtronics.com

bookmark this page

Transtronics, Inc.

3209 W.9th street
Lawrence, KS 66049
USA

phone (785) 841 3089
FAX (785) 841 0434
E-mail inform@xtronics.com
WEB
http://www.xtronics.com

Corporate information and privacy statement
(C) Copyright 1994-2006, Transtronics, Inc. All rights reserved
Transtronics® is a registered trademark of Transtronics, Inc.